ZGXH-2R24-5a Signal SPD User Manual
General
Standard compliance: GB/T 18802.21-2004 and Q/75875187-9.3-2011.
This product is connected to the front end of the protected equipment and is used to protect the high-speed Ethernet interface circuit. Both the input and output ends are shielded RJ45 sockets.
It uses category 5 shielded twisted pair cables with RJ45 plugs to connect with the protected equipment.
The protector features a fast response speed, a high transmission rate and a low protection level.
Operating Environment
Temperature range: –40°C to 70°C; relative humidity: ≤90%; air pressure: 86 kPa to 106 kPa.
Working Principles
Connected in series in front of a protected equipment, this SPD diverts lightning current to ground through its lightning circuit when the transmission line suffers from lightning induction. In addition, the SPD clamps lightning overvoltage to a level allowed by the equipment, thereby ensuring security of the equipment.
Technical Parameters
Connection
Mode |
RJ45 |
Impulse withstand capability 1.2/50 μs; 8/20 μs |
L-L |
L-PE |
| 0.6 kV, 0.3 kA |
4 kV, 2 kA |
| Protected pin |
1, 2; 3, 6 |
Impulse limiting voltage (1)
1.2/50 μs; 8/20 μs
|
L-L |
L-PE |
| ≤ 70 V |
≤ 700 V |
| Operating voltage |
5 V |
Impulse limiting voltage (2)
1 kV/μs
|
L-L |
L-PE |
| ≤ 35 V |
≤ 300 V |
| Transmission rate |
100 Mbit/s |
Dimensions
(H x W x D) mm
|
482 mm ×141.5 mm ×44 mm
|
Limiting voltage
10/700 μs |
L-L |
L-PE |
Weight |
2400 g
|
| ≤ 30 V |
≤ 50 V |
Exterior
The protector adopts the form of a standard 19-inch chassis and can be directly installed on the rack.
Both the input and output are RJ45 sockets.